Find the right generator
Answer 4 questions: we calculate the power and point you to the right generator.
4 steps · free PDF report · checked by our team
- CoolingWhich type of generator?
- UseWhat is it for?
- PowerDo you know the power you need?
- PreferencesYour preferences
How to work out the generator size you need
List your appliances. Multiply each appliance's power (in watts) by how many you have, then add them up. That is the total connected load, in kW. If you already know the total load, enter it directly (method B).
Allow for simultaneous use. Not everything runs at once. With method A, the finder applies a factor for your application, from 0.6 (hotel, school) to 0.9 (telecom site). You can also pick high use (×0.9) or low use (×0.6). With method B, the load you enter is used as is.
Convert to kVA. A generator is chosen in kVA, which is apparent power. With a power factor of 0.8: kVA = kW ÷ 0.8.
Add a 25% reserve. This way the generator does not run at full load all the time.
Check the largest motor's start-up. When it starts, a motor (air conditioner, pump, compressor, elevator) draws several times its running power. The finder counts ×3 direct-on-line, ×2 star-delta, ×1.5 with a soft starter and ×1.2 with a variable-speed drive. It adds this surge to the load of everything else, then a 10% margin. It keeps the larger of the two values: the 25% reserve or the start-up requirement.
Correct for the site. Above 1,000 m altitude, a generator loses about 3.5% of its power per 300 m, up to 25%. Above 40 °C, it loses about 2% per 5 °C, up to 20%. In Kinshasa (about 300 m and 32 °C), no correction is needed.
Plan ahead. Add 10, 20 or 30% if more equipment is planned.
Pick the generator. The finder keeps the smallest generator whose rating covers the need. It compares the need with prime power for continuous use, or with standby power if the generator only runs during outages. It also shows the next smaller and the next larger model for comparison.
Example: a house in Kinshasa
Water-cooled set, 10 lights of 100 W, 4 air conditioners of 1,500 W, 2 refrigerators of 300 W and a 1,100 W water pump, with low simultaneous use:
| Total connected load | 8.7 kW |
|---|---|
| Simultaneous use (×0.6) | 5.2 kW |
| Apparent power (÷ PF 0.8) | 6.5 kVA |
| + 25% reserve | 8.2 kVA |
| Largest motor start (1.5 kW ×3) | 5.6 kVA surge |
| Step-load requirement (+10%) | 11.3 kVA |
| Required capacity | 11.3 kVA |
Result: 11.3 kVA. The finder recommends the 13 kVA water-cooled diesel generator (403A-15G1, 13 kVA · 10.4 kW), or the 15 kVA · 12 kW model for extra headroom.
Typical power values used by the finder
| Appliance | Default power | Motor |
|---|---|---|
| Lighting | 100 W | No |
| Air conditioner | 1,500 W | Yes |
| Refrigerator | 300 W | Yes |
| Freezer | 400 W | Yes |
| Television | 120 W | No |
| Computer | 200 W | No |
| Printer | 500 W | No |
| Server | 800 W | No |
| Office equipment | 300 W | No |
| Water pump | 1,100 W | Yes |
| Electric motor | 2,200 W | Yes |
| Elevator | 7,000 W | Yes |
| Medical equipment | 1,500 W | No |
| Welding machine | 4,000 W | Yes |
| Compressor | 2,200 W | Yes |
| Construction equipment | 3,000 W | Yes |
| Industrial machinery | 5,000 W | Yes |
| Refrigeration equipment | 2,000 W | Yes |
Default values in the tool. Check your appliances' rating plates: every value can be changed in the finder.
kVA and kW: how they relate
kW is the useful power your appliances consume. kVA is the apparent power the generator must supply. With a power factor of 0.8: kW = kVA × 0.8.
| Generator (kVA, prime) | Power (kW) | MK model (Perkins engine) |
|---|---|---|
| 13 kVA | 10.4 kW | 403A-15G1 |
| 20 kVA | 16 kW | 404A-22G1 |
| 30 kVA | 24 kW | 1103A-33G |
| 45 kVA | 36 kW | 1103A-33TG1 |
| 60 kVA | 48 kW | 1103A-33TG2 |
| 100 kVA | 80 kW | 1104C-44TAG2 |
| 150 kVA | 120 kW | 1106A-70TAG2 |
| 200 kVA | 160 kW | 1106A-70TAG4 |
| 300 kVA | 240 kW | 1506A-E88TAG5 |
| 500 kVA | 400 kW | 2506A-E15TAG2 |
| 1,000 kVA | 800 kW | 4008-30TAG2 |
| 2,000 kVA | 1,600 kW | 4016-61TRG2 |
Prime or standby rating
Prime power is what the generator can deliver for unlimited hours per year under a varying load. Standby power is higher, but it is meant for outages only. Our datasheets give both: for example 100 kVA · 80 kW prime and 110 kVA · 88 kW standby for the set with the Perkins 1104C-44TAG2 engine. Pick “Standby” in the finder if the generator only runs during outages. When unsure, the calculation uses prime power. Our guide to prime and standby ratings sets out the ISO 8528-1 definitions.
Air-cooled or water-cooled?
MK Energies offers 18 air-cooled generators (Bison and Brux: gasoline, inverter or small diesel) from 2 kW (gasoline) to 15 kVA (diesel), single- or three-phase. We also offer 25 water-cooled Perkins-engine diesel generators from 13 to 2,000 kVA, three-phase. Gasoline and inverter sets are rated in kW. If your need falls outside the range you chose, the finder points you to the other one.
Sizing FAQ
How do I work out the size of a generator?
Add up your appliances' power in kW, then apply a simultaneous-use factor. Divide by 0.8 to get kVA and add a 25% reserve. With motors (air conditioners, pumps, compressors), also check the start-up surge of the largest motor. The finder does this calculation and shows every step.
What is the difference between kVA and kW when sizing a generator?
kW is the useful power of your appliances. kVA is the apparent power the generator must supply. For a generator a power factor of 0.8 is used: kW = kVA × 0.8. A 100 kVA generator therefore supplies 80 kW.
Why do air conditioners and pumps need more power?
When it starts, an electric motor draws several times its running power. The finder counts ×3 for direct-on-line starting, ×2 for star-delta, ×1.5 with a soft starter and ×1.2 with a variable-speed drive. This surge is added to the load of the other appliances, with a 10% margin.
Prime or standby rating: which one should I use?
If the generator runs for long hours or every day, size it on prime power. If it only runs during outages, the finder compares your need with the higher standby rating. If unsure, choose “Not sure”: the calculation then uses prime power.
Air-cooled or water-cooled: which should I choose?
An air-cooled generator is compact and affordable for occasional or mobile use. Our range goes from 2 kW (gasoline and inverter sets) to 15 kVA. A water-cooled generator runs long hours under heavy load. Our Perkins-engine range goes from 13 to 2,000 kVA, three-phase. If your need falls outside a range, the finder points you to the other one.
Does the finder account for altitude and heat?
Yes. Above 1,000 m altitude, it increases the required capacity by about 3.5% per 300 m, up to 25%. Above 40 °C, it increases it by about 2% per 5 °C, up to 20%. The defaults match Kinshasa (about 300 m and 32 °C), where no correction is applied.
Do I need a single-phase or three-phase generator?
Water-cooled Perkins-engine generators are three-phase. The air-cooled range includes single-phase and three-phase models. If you don't know, choose “Not sure”: the finder considers both and our team will confirm.
Is the finder's result final?
No, it is a first recommendation. Final sizing must be confirmed by the MK Energies technical team. The team also handles delivery in Kinshasa and to the provinces, installation and maintenance.
How much does the recommended generator cost?
Prices are given on request. They depend on the model, the version (soundproof or open frame) and availability. Send your result by WhatsApp or email to get a quote.
Can I rent a generator for a limited period?
Yes. MK Energies also rents out generators. Describe your need (capacity, duration, location) and we will propose a solution.